Miniature Circuit Breaker MCB
Technical Parameters:
Rated voltage(V) | Poles | Rated current(A) | Rated short circuit breaking capacity | |
230 | 1.2 | 6.10.16.20 | Test breaking capacity(KA) | Power factor |
230/400 | 1.2 | 25.32 | 4.5 | 0.65~0.70 |
400 | 2.3.4 | 40 | 4.5 | |
230 | 1.2 | 50.63 | 4.5 | |
230/400 | 1.2 | 4.5 | 0.75~0.80 | |
400 | 2.3.4 | 4.5 | ||
Current Release Character Diagram:
Test current(A) | Rated current(A) | Requested time | Result | Start station | Remark |
1.13In | all | t>=1h | Don’t trip | Cool | |
1.45In | All | T<1h | trip | heat | Current ascends the requested value stably in 5s |
2.55In | In<=32A | 1s<t<60s | trip | Cool | Auxiliary switch closed, power is on |
2.55In | In>32A | 1s<t<120s | trip | Cool | Auxiliary switch closed, power is on |
5In(Cmode) | All | t>=0.1s | Don’t trip | Cool | Auxiliary switch closed, power is on |
10In(Cmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
10(Dmode) | All | t>=0.1s | Don’t trip | Cool | Auxiliary switch closed, power is on |
14In(Dmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
Features: | Overload/short circuit protection |
Product number: | DZ47-63/2P |
Installation size: | 18*76*66mm |
Rated current: | 6-63A |
Rated voltage: | 230V/400V |
Breaking capacity: | 4500A |
proper temperature: | -5~40 |
Shell material: | Flame retardant PC material |
Installation form: | Standard rail installation |
certified product: | 3C certification |
Products real shot:
PV Series Circuit Breaker | DZ47-63 | |||
Frame degree rated current(A) | 63A | |||
Ue Rated operating voltage (V DC) | DC550V | DC800V | DC1000V | DC1200V |
Rated Current In (A) | 6-10-16-20-25-32-40-50-63 | |||
Rated insulation voltage Ui (V DC) | 2P: 800V 4P:1200V | |||
Rated Impact voltage Uimp (kV) | 4 | |||
Ultimate breaking capacity lcu (kA) | 6 | 6 | 6 | 6 |
Run breaking capacity lcs (%lcu) | 75% | 75% | 75% | 75% |
Curve type | C | |||
Trip type | Thermal-magnetic | |||
MECHANICAL | 20000 | |||
8500 | ||||
ELECTRIC | 2500 | |||
1500 | ||||
Shunt release (SHT) | Option | |||
Undervoltage release (UNT) | ||||
Auxiliary contact (AX) | ||||
Alarm contact (AL) | ||||
Wiring capacity (mm²) | In≤32A,1∼25mm²,1≥40A,10∼35mm² | |||
Ambient temperature (℃) | -20∼70 | |||
Altitude | ≤2000 | |||
Relative humidity | ≤95% | |||
Pollution Level | 3 | |||
Installation Environment | No obvious shock and vibration | |||
Installation category | Class lll | |||
Installation | DIN Standard rail |
Q1: Are you a circuit breaker factory or a circuit breaker from a trading company?
A1: We are a factory of circuit breaker.
Q2: Can samples be provided for free?
A2: Samples can be provided, but the sample cost should be paid by you. Sample fees will be refunded after further ordering.
Q3: Do you accept customized orders?
A3: Yes. We can provide OEM, ODM services.
Q4: What is the payment term?
A4: We accept TT, 30% deposit and 70% balance before give delivery.
Q5: When is the delivery time?
A5: It usually takes 15-25 days to confirm payment after LY, but the specific time should be based on the order quantity.
Q6: Tell me the standard of package?
A6: Export standard package or special package according to customer requirement.
Contact Person : | Joyce Wang |
---|